Ventilátor, 230V
Číslo výrobku: 251437
Decentralized mechanical extract ventilation, constant flow
Single flow decentralised mechanical ventilation unit for continuous running, Ø100mm, constant volume and low consumption. Ideal for
application in bathroom, toilet and small/medium premises. Suitable to extract stale air directly to the outside or through medium-long length ducting.
Units can be wall/panel, ceiling and window mounted.
Casing made of high quality ABS provides long lasting shock-proof and robust construction. The unit is finished in white RAL 9010 and are UV resistant.
High efficient mixed flow impeller, providing enhanced aerodynamic properties, low noise and increased performances.
EC brushless motor with integral thermal protection, mounted on sealed for life high quality ball bearings to assure a longer fan life and
ideal for cold climates.
Ekodesign | ||
---|---|---|
Vyhovuje ErP | 2018 | |
Kategorie jednotky | RVU | |
Typ pohonu | Externí ochrana motoru nebo reg. otáček (MSD nebo VSD) | |
Typ jednotky | UVU | |
Typ rekuperace (ZZT) | Žádný | |
Tepelná účinnost rekuperace (UVU) | Neuplatňuje se | |
qv nom | 0,0208 | m³/s |
P nom | 0,005 | kW |
Ps nom | 25 | Pa |
Účinnost ventilátoru | 11,2 | % |
Základní provedení | ||
---|---|---|
Vyhovuje ErP | 2018 | |
SEC průměrné klima | -14,36 | kWh/(m².a) |
SEC chladné klima | -30,76 | kWh/(m².a) |
SEC teplé klima | -4,97 | kWh/(m².a) |
SEC třída | E | |
Kategorie jednotky | RVU | |
Typ jednotky | UVU | |
Typ pohonu | Externí ochrana motoru nebo reg. otáček (MSD nebo VSD) | |
Typ rekuperace (ZZT) | Žádný | |
Tepelná účinnost rekuperace (UVU) | Neuplatňuje se | |
qv max | 75 | m³/h |
P max | 5 | W |
qv ref | 0,0144 | m³/s |
Ps ref | 50 | Pa |
SPI | 50 | W/(m³/h) |
CTRL | 1 | |
MISC | 1,1 | |
Hodnota x | 1,5 | |
Vnější netěsnost | Neuplatňuje se | |
AEC průměrné klima | 112 | kWh |
AHS chladné klima | 112 | kWh |
AEC teplé klima | 112 | kWh |
AHS průměrné klima | 17 | kWh/rok |
AHS chladné klima | 34 | kWh/rok |
AHS teplé klima | 8 | kWh/rok |
Jednotka s příslušenstvím | ||
---|---|---|
Vyhovuje ErP | 2018 | |
SEC průměrné klima | 26,84 | kWh/(m².a) |
SEC chladné klima | 53,9 | kWh/(m².a) |
SEC teplé klima | 11,33 | kWh/(m².a) |
SEC třída | B | |
Kategorie jednotky | RVU | |
Typ jednotky | UVU | |
Typ pohonu | Externí ochrana motoru nebo reg. otáček (MSD nebo VSD) | |
Typ rekuperace (ZZT) | Žádný | |
Tepelná účinnost rekuperace (UVU) | Neuplatňuje se | |
qv max | 75 | m³/h |
P max | 5 | W |
qv ref | 0,0144 | m³/s |
Ps ref | 50 | Pa |
SPI | 0,089 | W/(m³/h) |
CTRL | 0,65 | |
MISC | 1,1 | |
Hodnota x | 1,5 | |
Vnější netěsnost | Neuplatňuje se | |
AEC průměrné klima | 58 | kWh |
AEC chladné klima | 58 | kWh |
AEC teplé klima | 58 | kWh |
AHS průměrné klima | 28 | kWh/rok |
AHS chladné klima | 55 | kWh/rok |
AHS teplé klima | 13 | kWh/rok |
Nominální údaje | ||
---|---|---|
Napětí (jmenovité) | 230 | V |
Frekvence | 50 | Hz |
Fáze | 1~ | |
Příkon (P1) | 5 | W |
Proud | 0,072 | A |
Otáčky ventilátoru | 2.680 | ot/min. |
Průtok vzduchu [m³/h] | 0 až 106 | m³/h |
Maximální teplota média | max 50 | °C |
Hlukové údaje | ||
---|---|---|
Hladina akustického tlaku ve 3 m (volný prostor) | 32 | dB(A) |
Ochrana/Klasifikace | ||
---|---|---|
Třída krytí, motor | IPX4 | |
Třída izolace | B |
Údaje dle ErP | ||
---|---|---|
Energetická třída, základní jednotka | B | |
Energetická třída, jednotka s příslušenstvím | E | |
Splňuje požadavky ErP: | ErP 2018 |
Rozměry a hmotnosti | ||
---|---|---|
Rozměry potrubí; Kruhové, sání | 100 | mm |
Hmotnost | 0,6 | kg |
Ostatní | ||
---|---|---|
Typ motoru | AC |
BF 100MX | □A | B | C | øD | E | [mm] |
164 |
46 |
82 |
99 |
101 |
Název souboru dokumentu | Typ dokumentu | |
---|---|---|
MANUAL_INSTALLATION_BF_100MX_MULTILINGUAL.PDF | Návod | |
BF_100MX_SYSTEMAIR.PDF | Technická dokumentace | |
DECLARATION_OF_CONFORMITY_BF__DMV__IF_EN_20230224_142301454.PDF | Prohlášení |