CXE/AVC Modbus

Артикулен номер: 37256

 

CXE/AV Control Modul

Speed control unit for up to 2 fans for the following functions:

- Temperature control

- volume flow control

- pressure control

- Air velocity control

Integrated voltage supply for sensors: +24 V, max. 70 mA

Integrated analog outputs A1 and A2: 0-10 V, Imax 10 mA (short-circuit-proof)

Maximum load of relays K1 and K2: AC 250 V / 2 A

Maximum ambient temperature: +55 °C

Interference emission according to EN 61000-6-3

Interference immunity according to EN 61000-6-2

Setting of the desired speed through device or by external default, e.g. 0-10 V

Connecting pressure sensors (refrigeration), measuring range 0-30 bar, 0-50 bar

Connecting temperature sensors, device measuring range -27...+75 °C, Sensor measuring range -10...+120 °C

Connecting differential pressure sensors (air conditioning), measuring range 0-6000 Pa, acquisition of volume flows up to 65,000 m3/h

Connecting air velocity sensors, measuring range 0-1 m/s, 0-10 m/s

Connecting additional sensors, e.g. combination sensors, CO2, sensor signal 0-10 V / 0-20 mA / 4-20 mA

Several sensors can be combined with the CXE/AV universal control module. The actual value measured at the sensor is compared with the setpoint. This results in the 0-10 V output signal. Two 0-10 V outputs are integrated. These serve to activate EC fans, frequency inverters or other devices.

Optionally, connected field devices (frequency inverters/EC fans with plugged MODBUS add-on module) can be activated by the integrated MODBUS-RTU interface (MODBUS Master function). The device also contains two separate control circuits, a real time clock and timer functions.

The universal control modules are especially suitable for the following applications: Refrigeration, air conditioning, general ventilation tasks, clean room technology. For typical applications in the areas mentioned, fast start-up is possible by selecting pre-programmed operating modes.

Технически параметри

Номинални данни
Напрежение (номинално) 230 V
Честота 50; 60 Hz
Фази 1~
Защита/Класификация
Клас на корпуса IP54
Контролер и сензори
Позволена влажност, не-кондензираща 0 до 85 %RH
Температура на околната среда и въздуховода
Позволена температура на околната среда -20 до 55 °C
Размери и тегла
Тегло 0,9 kg

Thewiring diagram can be found as PDF file at the documentation.

Images Dimensions - CXE/AVC Modbus - systemair

 

A B C D E F

CXE/AVC

223

200

198

137

23

115